Products » PLC I/O Wiring Systems (Fused and Unfused) » 16 Way Fused Digital Output Modules
Item #21
Save time and cost while protecting your valuable automation investment.
Note: PLC to module wiring assembly is not included with the fuse block - order separately. Cabling comes factory assembled and tested- just plug it in, connect the field wiring and run.
This product is designed to meet Council Directive 73/23/EEC low voltage, by applying the safety requirements EN 61131-2. This equipment is classified as open equipment and must be installed (mounted) in an enclosure during operation as a means of providing safety protection
| Specifications | |
| Number of Outputs | 16 |
| Normal Voltage Range | 10 to 32VDC |
| Maximum Voltage | 60VDC |
| Fuse Type | Self Resetting PolyFuse |
| Fuse Current | Hold: 750mA per output Trip: 1.5A per output |
| One Hour Post Trip Resistance | 0.6 Ohms |
| Module Current | 2.5 Amps @ 24VDC |
| Initial Resistance @ 25 ºC | Min: 0.25 Ohms, Max: 0.40 Ohms |
| Thermal Dissipation | 10.37 BTU/hr @ 60 ºC |
| Termination | Spring Clamp |
| Field Conductor Size | Solid - 0.2 to 2.5mm Flexible - 0.2 to 1.5mm AWG - 24 to 14 |
| Mounting | DIN Rail EN50 022,35,45 |
| Operating Temperature | 0 to 60 ºC |
| Storage Temperature | 0 to 85 ºC |
| Relative Humidity | 5 to 95% non condensing |
| 16-Way Dimensions (L x W x H) (mm) | 102 x 78 x 53 |
| 32-Way Dimensions (L x W x H) (mm) | 183 x 78 x 53 |
| Power LED Indicator | Off = 24VDC supply not connected On = 24VDC supply connected |
| Output LED Indicators | Off = Output Off Green = Output On and fuse OK Red = Output On and fuse blown |