Products » PLC I/O Wiring Systems (Fused and Unfused) » 16 Way Fused Digital Input Modules
Item #63
Save time and cost while protecting your valuable automation investment.
Note: PLC to module wiring assembly is not included with the fuse block - order separately. Cabling comes factory assembled and tested- just plug it in, connect the field wiring and run.
This product is designed to meet Council Directive 73/23/EEC low voltage, by applying the safety requirements EN 61131-2. This equipment is classified as open equipment and must be installed (mounted) in an enclosure during operation as a means of providing safety protection
| Number of Inputs | 16 |
| Normal Voltage Range | 10 to 32VDC |
| Maximum Voltage | 48VDC |
| Input Type | Sinking |
| Module Current | 2 Amps @ 24VDC |
| Fuse Group Current | 250mA @ 24VDC |
| Termination | Spring Clamp |
| Field Conductor Size | Solid - 0.2 to 2.5mm Flexible - 0.2 to 1.5mm AWG - 24 to 14 |
| Mounting | DIN Rail EN50 022,35,45 |
| Operating Temperature | 0 to 60 degrees C |
| Storage Temperature | 0 to 85 degrees C |
| Relative Humidity | 5 to 95% non condensing |
| 16-Way Dimensions (L x W x H) (mm) | 102 x 78 x 53 |
| 32-Way Dimensions (L x W x H) (mm) | 183 x 78 x 53 |
| Power LED Indicator | Off = 24VDC supply not connected On = 24VDC supply connected |
| Input LED Indicators | Off = Input Off On = Input On |
| Fuse LEDs Indicators | Off = 24VDC supply not connected Green = Fuse OK Red = Fuse blown |
|
Ordering Information |
|
|
TCS Part Number |
Description |
|
003-2011-000 |
MOP-16DI-0 (terminals labelled 0-15) |
|
003-2011-002 |
MOP-16DI-1 (terminals labelled 1-16) |
|
003-2012-000 |
MOP-32DI-0 (terminals labelled 0-31) |
|
003-2012-002 |
MOP-32DI-1 (terminals labelled 1-32) |